(1) Where more than one hydrant is required to provide the number of jets required by Regulation 98(1), a fire main shall be provided.
(2) Materials readily rendered ineffective by heat shall not be used for fire mains, unless adequately protected.
(3) Where fire pump delivery pressure can exceed the designed working pressure of fire mains, relief valves shall be fitted.
(4) Fire mains shall have no connexions other than those required for fire fighting, except for the purposes of washing the deck and anchor chains or operating the chain locker bilge ejector.
(5) Where fire mains are not self-draining, suitable drain cocks shall be fitted where frost damage may be expected.
(2) Materials readily rendered ineffective by heat shall not be used for fire mains, unless adequately protected.
(3) Where fire pump delivery pressure can exceed the designed working pressure of fire mains, relief valves shall be fitted.
(4) Fire mains shall have no connexions other than those required for fire fighting, except for the purposes of washing the deck and anchor chains or operating the chain locker bilge ejector.
(5) Where fire mains are not self-draining, suitable drain cocks shall be fitted where frost damage may be expected.