Internationaal Verdrag van Torremolinos voor de beveiliging van vissersvaartuigen, 1977
(1) At least two fire pumps shall be provided.
(2) If a fire in any one compartment could put all the fire pumps out of action, there shall be an alternative means of providing water for fire fighting. In vessels of 75 metres in length and over this alternative means shall be a fixed emergency fire pump independently driven. This emergency fire pump shall be capable of supplying two jets of water to the satisfaction of the Administration.
(3) (a) The fire pumps, other than the emergency pump shall be capable of delivering for fire fighting purposes a quantity of water at a minimum pressure of 0.25 newtons per square millimetre, with a total capacity (Q) of at least: where L, B and D are in metres. However, the total required capacity of the fire pumps need not exceed 180 cubic metres per hour.
(b) Each of the required fire pumps other than any emergency pump shall have a capacity not less than 40 per cent of the total capacity of fire pumps required by sub-paragraph (a) and shall in any event be capable of delivering at least the jets of water required by Regulation 80(2)(a). These fire pumps shall be capable of supplying the fire main systems under the required conditions. Where more than two pumps are installed the capacity of such additional pumps shall be to the satisfaction of the Administration.
(a) The fire pumps, other than the emergency pump shall be capable of delivering for fire fighting purposes a quantity of water at a minimum pressure of 0.25 newtons per square millimetre, with a total capacity (Q) of at least: where L, B and D are in metres. However, the total required capacity of the fire pumps need not exceed 180 cubic metres per hour.
(b) Each of the required fire pumps other than any emergency pump shall have a capacity not less than 40 per cent of the total capacity of fire pumps required by sub-paragraph (a) and shall in any event be capable of delivering at least the jets of water required by Regulation 80(2)(a). These fire pumps shall be capable of supplying the fire main systems under the required conditions. Where more than two pumps are installed the capacity of such additional pumps shall be to the satisfaction of the Administration.
(4) (a) Fire pumps shall be independently driven power pumps. Sanitary, ballast, bilge or general service pumps may be accepted as fire pumps, provided that they are not normally used for pumping oil and that, if they are subject to occasional duty for the transfer or pumping of fuel oil, suitable change-over arrangements are fitted.
(b) Relief valves shall be provided in conjunction with all fire pumps if the pumps are capable of developing a pressure exceeding the design pressure of the water service pipes, hydrants and hoses. These valves shall be so placed and adjusted as to prevent excessive pressure in any of the fire main systems.
(c) Emergency power-operated fire pumps shall be independently driven self-contained pumps either with their own diesel engine prime mover and fuel supply fitted in an accessible position outside the compartment which contains the main fire pumps, or be driven by a self-contained generator, which may be the emergency generator referred to in Regulation 55, of sufficient capacity and which is positioned in a safe place outside the engine room and preferably above the working deck. The emergency fire pump shall be capable of operating for a period of at least 3 hours.
(d) Emergency fire pumps, sea-suction valves and other necessary valves shall be operable from outside compartments containing main fire pumps in a position not likely to be cut off by a fire in those compartments.
(a) Fire pumps shall be independently driven power pumps. Sanitary, ballast, bilge or general service pumps may be accepted as fire pumps, provided that they are not normally used for pumping oil and that, if they are subject to occasional duty for the transfer or pumping of fuel oil, suitable change-over arrangements are fitted.
(b) Relief valves shall be provided in conjunction with all fire pumps if the pumps are capable of developing a pressure exceeding the design pressure of the water service pipes, hydrants and hoses. These valves shall be so placed and adjusted as to prevent excessive pressure in any of the fire main systems.
(c) Emergency power-operated fire pumps shall be independently driven self-contained pumps either with their own diesel engine prime mover and fuel supply fitted in an accessible position outside the compartment which contains the main fire pumps, or be driven by a self-contained generator, which may be the emergency generator referred to in Regulation 55, of sufficient capacity and which is positioned in a safe place outside the engine room and preferably above the working deck. The emergency fire pump shall be capable of operating for a period of at least 3 hours.
(d) Emergency fire pumps, sea-suction valves and other necessary valves shall be operable from outside compartments containing main fire pumps in a position not likely to be cut off by a fire in those compartments.
(2) If a fire in any one compartment could put all the fire pumps out of action, there shall be an alternative means of providing water for fire fighting. In vessels of 75 metres in length and over this alternative means shall be a fixed emergency fire pump independently driven. This emergency fire pump shall be capable of supplying two jets of water to the satisfaction of the Administration.
(3) (a) The fire pumps, other than the emergency pump shall be capable of delivering for fire fighting purposes a quantity of water at a minimum pressure of 0.25 newtons per square millimetre, with a total capacity (Q) of at least: where L, B and D are in metres. However, the total required capacity of the fire pumps need not exceed 180 cubic metres per hour.
(b) Each of the required fire pumps other than any emergency pump shall have a capacity not less than 40 per cent of the total capacity of fire pumps required by sub-paragraph (a) and shall in any event be capable of delivering at least the jets of water required by Regulation 80(2)(a). These fire pumps shall be capable of supplying the fire main systems under the required conditions. Where more than two pumps are installed the capacity of such additional pumps shall be to the satisfaction of the Administration.
(a) The fire pumps, other than the emergency pump shall be capable of delivering for fire fighting purposes a quantity of water at a minimum pressure of 0.25 newtons per square millimetre, with a total capacity (Q) of at least: where L, B and D are in metres. However, the total required capacity of the fire pumps need not exceed 180 cubic metres per hour.
(b) Each of the required fire pumps other than any emergency pump shall have a capacity not less than 40 per cent of the total capacity of fire pumps required by sub-paragraph (a) and shall in any event be capable of delivering at least the jets of water required by Regulation 80(2)(a). These fire pumps shall be capable of supplying the fire main systems under the required conditions. Where more than two pumps are installed the capacity of such additional pumps shall be to the satisfaction of the Administration.
(4) (a) Fire pumps shall be independently driven power pumps. Sanitary, ballast, bilge or general service pumps may be accepted as fire pumps, provided that they are not normally used for pumping oil and that, if they are subject to occasional duty for the transfer or pumping of fuel oil, suitable change-over arrangements are fitted.
(b) Relief valves shall be provided in conjunction with all fire pumps if the pumps are capable of developing a pressure exceeding the design pressure of the water service pipes, hydrants and hoses. These valves shall be so placed and adjusted as to prevent excessive pressure in any of the fire main systems.
(c) Emergency power-operated fire pumps shall be independently driven self-contained pumps either with their own diesel engine prime mover and fuel supply fitted in an accessible position outside the compartment which contains the main fire pumps, or be driven by a self-contained generator, which may be the emergency generator referred to in Regulation 55, of sufficient capacity and which is positioned in a safe place outside the engine room and preferably above the working deck. The emergency fire pump shall be capable of operating for a period of at least 3 hours.
(d) Emergency fire pumps, sea-suction valves and other necessary valves shall be operable from outside compartments containing main fire pumps in a position not likely to be cut off by a fire in those compartments.
(a) Fire pumps shall be independently driven power pumps. Sanitary, ballast, bilge or general service pumps may be accepted as fire pumps, provided that they are not normally used for pumping oil and that, if they are subject to occasional duty for the transfer or pumping of fuel oil, suitable change-over arrangements are fitted.
(b) Relief valves shall be provided in conjunction with all fire pumps if the pumps are capable of developing a pressure exceeding the design pressure of the water service pipes, hydrants and hoses. These valves shall be so placed and adjusted as to prevent excessive pressure in any of the fire main systems.
(c) Emergency power-operated fire pumps shall be independently driven self-contained pumps either with their own diesel engine prime mover and fuel supply fitted in an accessible position outside the compartment which contains the main fire pumps, or be driven by a self-contained generator, which may be the emergency generator referred to in Regulation 55, of sufficient capacity and which is positioned in a safe place outside the engine room and preferably above the working deck. The emergency fire pump shall be capable of operating for a period of at least 3 hours.
(d) Emergency fire pumps, sea-suction valves and other necessary valves shall be operable from outside compartments containing main fire pumps in a position not likely to be cut off by a fire in those compartments.